MENU

Fun & Interesting

Continuity, Polarity and Insulation Resistance of our 2 way and Intermediate Lighting Circuit

GSH Electrical 66,182 lượt xem 7 years ago
Video Not Working? Fix It Now

Students training aid for testing continuity of the CPC and polarity of a 2 way and intermediate lighting circuit. Full demonstration using a MFT Megger tester set on the ohms scale.

Demonstration shows how to set up your Megger MFT tester and carry out an insulation resistance test for a 2 way lighting circuit. Test voltage is 500V DC and the minimum acceptable value according to BS 7671 is 1 megohms with further investigation when the reading falls below 2 megohms. Also shows and explains the need to switch both 2 way switches into the other on position and repeat the insulation resistance test.

= 🕐 Time Stamps - Cut to the action 🕕 ==

00:00 - Testing for continuity of CPC, polarity and insulation resistance
00:32 - Setting the Megger MFT up to measure resistance
01:15 - Link the line and CPC together
02:37 - Continuity of CPC and polarity test
05:01 - Insulation resistance test

Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.

You can follow me day by day on Facebook, Instagram and Twitter lookout for "GSH Electrical.

▶️ FACEBOOK https://www.facebook.com/gshelectrical/

▶️ INSTAGRAM https://instagram.com/p/BrIhZmrAYGDTmjMdb9lUNQodMevqsbDDki3qpQ0/

▶️ TWITTER https://mobile.twitter.com/gsh_electrical

▶️ TikTok https://vm.tiktok.com/ZMRBLFdhe/

#GSHElectrical #Electricaltrainingvideos #electricaltesting

Comment