Students training aid for testing continuity of the CPC and polarity of a 2 way and intermediate lighting circuit. Full demonstration using a MFT Megger tester set on the ohms scale.
Demonstration shows how to set up your Megger MFT tester and carry out an insulation resistance test for a 2 way lighting circuit. Test voltage is 500V DC and the minimum acceptable value according to BS 7671 is 1 megohms with further investigation when the reading falls below 2 megohms. Also shows and explains the need to switch both 2 way switches into the other on position and repeat the insulation resistance test.
= 🕐 Time Stamps - Cut to the action 🕕 ==
00:00 - Testing for continuity of CPC, polarity and insulation resistance
00:32 - Setting the Megger MFT up to measure resistance
01:15 - Link the line and CPC together
02:37 - Continuity of CPC and polarity test
05:01 - Insulation resistance test
Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.