What can you do when faced with an RCD that keeps tripping. In this video Marcus explains how to carryout an RCD ramp test. This test can prove if an RCD is oversensitive by showing the electrician the amount of earth leakage current in milliamps that it takes to trip the installed RCD.
Marcus carries out the ramp test from the load side of the RCCB with the MCB's OFF therefore removing all the loads in circuit.
🔔 Subscribe for more free electrical training videos https://youtube.com/c/GSHElectrical?sub_confirmation=1
== 🕐 Time Stamps - Cut to the action 🕕 ==
00:00 - RCD ramp test
00:46 - Live test
01:17 - No loads connected (MCB's OFF)
02:08 - Current in milliamps
03:11 - Could plugged in electronic equipment be causing the RCD to trip
04:51 - Clamp meter
05:11 - Investigating a tripping RCD
Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.